- 7 -
Mode 2: Mode 3:
Voltage input
+32000
+16000
10V
5V
0
Gain
Offset
Digital
output
+32384
-384
Voltage i nput
+32000
+16000
5V
2.5V
0
Gain
Offset
Digital
output
+32384
-384
Mode 2 of CR#2 ~ CR#5 0 ~ +10V, Gain = 5V (16,000), Offset = 0V (0)
Mode 3 of CR#2 ~ CR#5 0 ~ +5V, Gain = 2.5V (16,000), Offset = 0V (0)
Range of digital conversion (Max./Min.) 0 ~ +32,000 (-384 ~ +32,384)
Mode 4:
Current input
+32000
+16000
-16000
20mA
-32000
-20mA
10mA
0
Gain
Offset
Digital
output
+32384
-32384
Mode 4 of CR#2 ~ CR#5 ±20mA, Gain = 10mA (16,000), Offset = 0mA (0)
Range of digital conversion (Max./Min.) ±32,000 (±32,384)
Mode 5: Mode 6:
Current input
+32000
+16000
20mA
10mA
0
Gain
Offset
Digital
output
+32384
-384
Current input
+32000
+16000
20mA12mA
0
Gain
Offset
Digital
output
+32384
-384
4mA
Mode 5 of CR#2 ~ CR#5 0 ~ +20mA, Gain = 10mA (16,000), Offset = 0mA (0)
Mode 6 of CR#2 ~ CR#5
+4 ~ +20mA, Gain = 12mA (19,200), Offset = 4mA
(6,400)
Range of digital conversion (Max./Min.) 0 ~ +32,000 (-384 ~ +32,384)
Adjust D/A Conversion Curve
Users can adjust the conversion curves according to the actual needs by changing the
Offset value (CR#32 ~ CR#33) and Gain value (CR#38 ~ CR#39).
Equation for voltage output Mode0: 0.3125mV = 20V/64,000


32000
)(10
16000
V
Offset
OffsetGainX
VY
Y=Voltage output, X=Digital input