EasyManuals Logo

Delta DVP06XA-E2 User Manual

Delta DVP06XA-E2
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #9 background imageLoading...
Page #9 background image
- 8 -
Equation for current output Mode1: 0.625μA = 20mA/32,000


32000
)(20
16000
mA
Offset
OffsetGainX
mAY
Y=Current output, X=Digital input
Equation for current output Mode2: 0.5μA = 16mA/32,000
Adopt the equation of current output Mode 1, substitute Gain for 19,200(12mA) and
Offset for 6,400(4mA)


32000
)(20
6400
16000
640019200 mAX
mAY
Y=Current output, X=Digital input
mode 0:
Digital input
10V
5V
-5V
+32000
-10V
-32000
+16000
0
Gain
Offset
Voltage
output
-32768
+32767
Mode 0 (CR#2 ~ CR#5) ±10V, Gain = 5V (16,000), Offset = 0V (0)
Range of digital conversion (Max./Min.) ±32,000 (-32,768 ~ +32,767)
mode 1:
Digital input
+32000+16000
20mA
10mA
0
Offset
Current
output
+32767
Gain
Mode 1 (CR#2 ~ CR#5) 0 ~ +20mAGain = 10mA (16,000), Offset = 0mA (0)
Range of digital conversion (Max./Min.) 0 ~ +32,000 (0 ~ +32,767)
mode 2:
Digital input
+32000+16000
20mA
12mA
0
Offset
Current
output
+32767
Gain
4mA
-6400
Mode 2 (CR#2 ~ CR#5) 4 ~ +20mAGain = 12mA (19,200), Offset = 4mA
(6,400)
Range of digital conversion (Max./Min.) 0 ~ +32,000 (-6400 ~ +32,767)