Chapter 9 SpecificationsMS300
188
9-6 Environment for Operation, Storage and Transportation
DO NOT expose the AC motor drive to a poor environment, such as one with dust, direct sunlight, corrosive/
inflammable gasses, humidity, liquids, or excessive vibration. The salt in the air must be less than 0.01 mg/cm
2
every year.
Environment
Installation
Location
IEC 60364-1/ IEC 60664-1 Pollution degree 2, Indoor use only.
Surrounding
Temperature
Operation
IP20 / UL Open Type
-2050C
-2060C with derating
IP40 / NEMA 1 / UL Type 1
-2040C
-2050C with derating
Side-by-side Installation
Storage
-4085C
Transportation
-2070C
Non-condensing, non-freezing
Rated Humidity
Operation
Maximum 90%
Storage /
Transportation
Maximum 95%
No water condensation
Air Pressure
Operation
86–106 kPa
Storage/
Transportation
70–106 kPa
Pollution Level
IEC 60721-3
Operation
Class 3C2; Class 3S2
Storage
Class 2C2; Class 2S2
Transportation
Class 1C2; Class 1S2
Concentrate prohibited
Altitude
< 1000 m (For altitudes > 1000 m, derate to use it.)
Package
Drop
Storage
ISTA procedure
1A (according to weight) IEC 60068-2-31
Transportation
Vibration
Operating
1.0 mm, peak to peak value range from 213.2 Hz;
0.72.0 G range from 13.255 Hz;
2.0 G range from 55512 Hz.
Compliance with IEC 60068-2-6
Non-operating
2.5 G peak, 5 Hz–2 kHz
0.015" maximum displacement
Impact
Operating
15 G, 11 ms
Compliance with IEC/EN60068-2-27
Non-operating
30 G
Table 9-11