Chapter 15 CANopen OverviewMS300 
 
643 
 
15-3-3 Using the Delta Standard (Old definition, only supports speed mode) 
15-3-3-1 Various mode control method (following the Delta old standard) 
If you want to use the Delta old standard to control the motor drive, follow these steps: 
1.  Wire the hardware (refer to Section 15-2 Wiring for CANopen). 
2.  Set the operation source: set Pr.00-21 to 3 for CANopen communication card control. 
3.  Set the frequency source: set Pr.00-20 to 6. Choose the source for the Frequency command 
from the CANopen setting. 
4.  Set Delta Standard (Old definition, only supports speed mode) as the control mode: Pr.09-40 
= 0 and Pr.09-30 = 0. 
5.  Set the CANopen station: set Pr.09-36; the range is among 1–127. When Pr.09-36 = 0, the 
CANopen slave function is disabled. Note that if an error appears (station address error CAdE 
or CANopen memory error CFrE) when you finish the station setting, set Pr.00-02 = 7 to reset. 
6.  Set the CANopen baud rate: set Pr.09-37 (CANBUS baud rate: 1 Mbps (0), 500 Kbps (1), 250 
Kbps (2), 125 Kbps (3), 100 Kbps (4) and 50 Kbps (5)) 
15-3-3-2 The control method under speed mode 
1.  Set the target frequency: set 2020-02, the unit is Hz, with 2 decimal places. For example, 
1000 is 10.00 Hz. 
2.  Operation control: set 2020-01 = 0002H for running, and set 2020-01 = 0001H for stopping.