5.3 DC Connection (from PV Array)
 The maximum open circuit voltage of the PV Array must not exceed
600V (RPI-H3) / 1000V (RPI-H5).
 The recommended PV power connect to inverter is 3600W (RPI-H3) /
5950W (RPI-H5).
 The device installed between PV Array and inverter must meet the rating of
voltage higher than this device’s maximum input voltage.
CAUTION !
WARNING !
 When doing DC wiring, please choose the proper wiring by connect to the
correct polarity.
 When doing DC wiring, please confirm that PV Array’s power switch is off.
DC wiring polarities are divided into positive and negative, which is as shown in
Figure 5-5. The connection shall be coherent with the indication marked on inverter.
Table 5-3 : Cable size
Figure 5-5 : DC Wiring illustration
Current Rating Wire size
DC 15 A (RPI-H3)
DC 17.5 A (RPI-H5)
2-3mm
2
/ 14 AWG
3-4mm
2
/ 12 AWG
PV-KBT 4/6
PV-KST 4/6
26
Wiring