ERROR
Message Possible cause Action
Solar1
High
(E30)
1. Actual Solar1 voltage is over
1000Vdc
2. Detection circuit malfunction
1. Modify the solar array setting, and
make the Voc less than 1000Vdc
2.
Check the detection circuit inside the
inverter
Solar2
High
(E31)
1. Actual Solar2 voltage is over
1000Vdc
2. Detection circuit malfunction
1. Modify the solar array setting, and
make the Voc less than 1000Vdc
2.
Check the detection circuit inside the
inverter
Insulation
(E34)
1. PV array insulation fault
2. Large PV array capacitance
between Plus to Ground or
Minus to Ground or both.
3. Detection circuit malfunction
1. Check the insulation of Solar inputs
2.
Check the capacitance, dry PV panel
if necessary
3.
Check the detection circuit inside the
inverter
Table 7-1 Error Message
Warning
Message Possible cause Action
Solar1
Low
(W01)
1.
Actual Solar1 voltage is under
the limit
2. Some devices were damaged
inside the inverter if the actual
Solar1 voltage is close to "0"
3. Detection circuit malfunction
1. Check the Solar1 voltage connection
to the inverter terminal
2. Check all switching devices in boost1
3. Check the detection circuit inside the
inverter
Solar2
Low
(W02)
1.
Actual Solar2 voltage is under
the limit
2. Some devices were damaged
inside the inverter if the actual
Solar2 voltage is close to "0"
3. Detection circuit malfunction
1.
Check the Solar2 voltage connection
to the inverter terminal
2.
Check all switching devices in boost2
3.
Check the detection circuit inside the
inverter
Table 7-2 Warning Message
43
Error message and Trouble Shooting