42
Pr.55
Slip Compensation
Parameter # 55
Parameter Name
Slip compensation
Factory Setting
d000.0
Units
0.1%
Parameter value
d000.0 - d010.0%
This parameter can be programmed while the drive is running.
This parameter is used to compensate for the nominal slip within a range of 0.0 -
10.0%. When the output current of the AC drive is greater than the motor no-load
current (Pr.53), the AC drive will adjust its output frequency according to Pr.55.
Example: If Pr. 04 is set at 60Hz and Pr. 55 is set at 10%, the drive will increase the
output frequency up to 6% under full load conditions to compensate for slip.
Pr.56
Reserved
Pr.57
Multi-function Indication Output Contact
Parameter # 57
Parameter Name
Multi-function indication output contact
RA-RC(NO), RB-RC(NC)
Factory Setting
d0000
Settings
d0000 Fault indicator
d0001 AC drive operational
d0002 Pre-set frequency attained
d0003 Desired frequency attained
d0004 Non-zero speed
d0005 Over-torque detection
d0006 Baseblock indicator
This parameter sets the multi-function programmable relay contact outputs. The
contact ratings are 250Vac @ 2A, 30Vdc @ 2A. Set parameter Pr.57 according to
the table listed above.