Do you have a question about the Delta VFD-MS300 Series and is the answer not in the manual?
Braking Unit | Built-in |
---|---|
Control Mode | V/F Control, Sensorless Vector Control |
Humidity | Less than 90% RH (non-condensing) |
Cooling Method | Fan cooling |
Enclosure Rating | IP20 |
Overload Capacity | 150% for 1 minute |
Communication Interface | RS-485 |
Protection Features | Overvoltage, undervoltage, overcurrent, overload, short circuit, overheating |
Output Voltage | 0 to Input Voltage |
Power Range | 0.2 kW to 22 kW |
Operating Temperature | -10°C to 50°C |
Storage Temperature | -20°C to 60°C |
Connect DCM to MI1 (FWD) and MI2 (REV) for remote stop/start control.
Connect potentiometer to +10V, AVI, and ACM for remote speed variation.
Set parameters 00.20, 00.21, and 02.00 for remote operation modes.
Factory default V/F curve settings for general applications.
V/F curve settings optimized for fan and hydraulic applications.
V/F curve settings for applications requiring high starting torque.
Wiring and connection must be performed by a registered electrician to avoid voiding warranty.
Check motor suitability and configure terminals for VFD supply (DELTA for 1ph).
Parameter 00.02 resets all settings to factory defaults for 50Hz.
Parameter 00.20 sets the source for master frequency command (e.g., analog input).
Parameter 00.21 selects the source for master operation command (e.g., external terminals).
Set parameters 01.00-05.04 to match motor nameplate specifications.
Perform auto-tuning (05-00) after entering motor parameters for optimal performance.
Description of the VFD control panel buttons and their functions.
Details on the display items and their corresponding keypad functions.