VFD-L Series Instruction Sheet
1
Preface
Thank you for choosing DELTA’s VFD-L series AC Drive. The VFD-L series is
manufactured using high-quality components, material and incorporating the
latest microprocessor technology available.
This manual will help in the installation, parameter setting, troubleshooting,
and daily maintenance of the AC motor drive. To guarantee safe operation of
the equipment, read the following safety guidelines before connecting power
to the AC motor drive. Keep this operating manual handy and distribute to all
users for reference.
Important Notes:
¾
AC input power must be disconnected before any maintenance. Do
not connect or disconnect wires while power is applied to the
circuit. Only qualified technicians should perform maintenance on
the VFD-L.
¾ A charge may still remain in the DC-link capacitor with hazardous
voltages even after the power has been turned off. To avoid personal
injury, do not remove the cover of the AC drive until all “DISPLAY
LED” lights on the digital keypad are off. Please note that there
are live components exposed when the AC drive is open,. Be careful
to not touch these live parts.
¾ The AC drive may be destroyed beyond repair if power is
misapplied to the input/output terminals. Never connect the AC
drive output terminals U/T1, V/T2, W/T3 directly to the AC main
circuit power supply.
¾ There are highly sensitive MOS components on the printed circuit
boards. These components are especially sensitive to static
electricity. To avoid damaging these components, do not touch the
circuit boards with metal objects or your bare hands.
¾ Ground the VFD-L using the ground terminal. The grounding
method must comply with the laws of the country where the AC
drive is to be installed.
2 Receiving and Inspection
This VFD-L AC drive has gone through rigorous quality control tests at the
factory before shipment. Since many things may happen during shipping,
please check for the following after receiving the AC motor drive.
Inspect the unit to insure it was not damaged during shipment.
Make sure that the part number indicated on the nameplate corresponds
with the part number of your order.
Nameplate Information: Example of 1HP230V
MODEL :VFD007L21A
INPUT :1PH/9.7A 3PH/5.1A 200-240V 50-60Hz
OUTPUT :3PH 0-240V 4.2A 1.6kVA 1HP
Freq. Range:1.0~400Hz
DELTA ELECTRONICS, INC. MADE IN XXXXX
007L21A0T610001
AC Drive Model
Input Spec.
Output Spec.
Output Freq. Range
Bar Code
Serial NO.
Model Explanation
VFD 007 L 21 A
version
A: standard
B: with EMI
Filter
VFD-L series
Input voltage
002:0.2kW
004:0.4kW
Applicable motor capacity
Variable Frequency Drive
007:0.75kW
015:1.5kW
D: PNP Mode
E: PNP Mode with EMI Filter
Serial Number Explanation
007L21A0 T 6 10 00
1
230V 1-PHASE 1HP(0.75kW)
Production number
Production week
Production year 2006
Production factory
T: Taoyuan W: Wujiang
Model
If there is any nameplate information not corresponding to your purchase
order or any problem, please contact your distributor.
Dimension
RARC + 10V AVIM0M1M2M3GND
STOP
RUN
FWD
REV
RUN
STOP
PROG
DATA
MODE
RESET
Do not connect AC power to output
WARNING
Read the user manual before operation.
Do not inspect components until LEDs
are turned off for at least 1min.
terminals (U,V,W).
MIN. MAX.
VFD-L
RS-485
=
,
230V IPHASE
0.75KW
3 Wiring
Basic Wiring Diagram
Users must connect wiring according to the circuit diagram shown below.
Please follow all National and State wiring codes, when wiring the VFD-L.
U/T1
V/T2
W/T3
IM
3~
RS-485
61
120VAC/28VDC 3A
+10V 10mA(MAX)
RJ-11
1:+EV
2:GND
3:SG-
4:SG+
R/L1
S/L2
T/L3
MCCB
Factory default settings
Power supply for Potentiometer
0 10VDC
VR 3K 5K
:~Ω
Master Freq. setting
Analog voltage
Analog current
Motor
Multi-function indication
output contacts
Factory default:
Fault Indication
Main circuit (power)
terminals
Control circuit terminals
Shielded leads
*If the AC Drive model is VFD002L11A/B, VFD004L11A/B, VFD002L21B, VFD004L21B
or VFD007L21B, please use power terminals R/L1 and S/L2.
*If the AC Drive model is VFD002L21A, VFD004L21A or VFD007L21A, 1-phase/3 phase
power may be used on R/L1, S/L2, T/L3. When VFD002L21A/VFD004L21A or
VFD007L21A use 1-phase power, please select any two of the three input terminals
R/L1, S/L2, T/L3.
*If the AC Drive model is VFD015L23A, single phase power is not allowed.
NOTE: Do not plug in a Modem or telephone line to the RS-485 communication port,
permanent damage may result. Terminals 1 & 2 are the power source for the
optional copy keypad and should not be used while using RS-485
communication.
Main C i rc ui t Powe r
Communication
po rt
AVI
GND
3
2
1
VR
+10V
R/L1
S/L2
T/L3
RA
RC
Common Signal
M0
M1
M2
GND
M3
Forward/Stop
Reverse/Stop
Reset
Multi-step 1
Figure 1 for models of VFD-L series
V
FD002L11A, VFD002L11B, VFD002L21A, VFD002L21B, VFD004L11A,
V
FD004L11B, VFD004L21A, VFD004L21B, VFD007L21A, VFD007L21B, VFD015L23A
U/T1
V/T2
W/T3
IM
3~
RS-485
61
010VDC
VR 3K 5K
:~Ω
AVI
GND
3
2
1
V
R
RJ-11
1:+EV
2:GND
3:SG-
4:SG+
R/L1
S/L2
T/L3
MCCB
M0
M1
M2
GND
M3
Factory default settings
Forward/Stop
Reverse/Stop
Reset
Multi-step 1
+15V 30mA(MAX)
Power supply
Master Freq. setting
Analog voltage
Analog current
Motor
Multi-function indication
output contacts
120VAC/28VDC 3A
Factory default:
Fault Indication
Main circuit (power)
terminals
Control circuit terminals
Shielded leads
Main C irc ui t Pow er
Communication
p or t
+15V
R/L1
S/L2
T/L3
3
2
1
VR
+15V
+15V 30mA(MAX)
Power supply
*If the AC Drive model is VFD004L21E, VFD007L21E, please use power terminals
R/L1 and S/L2.
*If the AC Drive model is VFD004L21D, VFD007L21D, 1-phase/3 phase power may be
used on R/L1, S/L2, T/L3. When VFD004L21D/VFD007L21D use 1-phase power, please
select any two of the three input terminals R/L1, S/L2, T/L3.
NOTE: Do not plug in a Modem or telephone line to the RS-485 communication port,
permanent damage may result. Terminals 1 & 2 are the power source for the
optional copy keypad and should not be used while using RS-485
co mm unica tio n.
VR: 3K 5K
~Ω
RA
RC
Figure 2 for models of VFD-L series
V
FD004L21D, VFD004L21E, VFD007L21D, VFD007L21E
Wiring for NPN mode and PNP mode
Factory
setting
NPN Mode for models:
VFD002L11A, VFD002L11B, VFD002L21A,
VFD002L21B, VFD004L11A, VFD004L11B,
VFD004L21A, VFD004L21B, VFD007L21A,
VFD007L21B, VFD015L23A
+10V
M0
M1
M2
M3
GND
*Don't apply the mains voltage directly
to above terminals.
FWD/STOP
REV/STOP
RESET
Multi -step 1
Digital Signal Common
E
*Don't apply the mains voltage directly
to above terminals.
FWD/STOP
REV/STOP
RESET
Multi-step 1
Factory
setting
PNP Mode for models:
VFD004L21D, VFD004L21E, VFD007L21D, VFD007L21E
+15V
M0
M1
M2
M3
GND
E
Main circuit wiring
Single phase models input from R/L1, S/L2
UP/DOWN
Function
Display key
Data
Confirmation key
RUN/STOP
RS485
communication
port
Grounding
Motor connections U/T1, V/T2, W/T3
Motor capacity
and input power
Frequency
setting
LED display
The signal selection
fo r AVI to in put
DC0~+10V
or 4~20 mA
groundingAC line input terminals
U/T1 V/T2 W/T3
R/L1 S/L2
T/L3
Control circuit wiring
RA RC +10V
AVI
M0
M1 M2 M3
GND
(120VAC
/
DC28V 3A)
Relay
Wire Gauge:22-24AWG, Torque: 4Kgf-cm
Multi-function indication
output contact
Power for speed setting
Analog Voltage, current
frequency command
Multi-function assistant terminal
Common si gnal
Multi-function input selection 1
Multi-function input selection 2
Multi-function input selection 3
Figure 3 for models: VFD002L11A, VFD002L11B, VFD002L21A, VFD002L21B, VFD004L11A,
VFD004L11B, VFD004L21A, VFD004L21B, VFD007L21A, VFD007L21B, VFD015L23A
RA RC
+15V
AVI
M0
M1 M2 M3
GND
(120VAC
/
DC28V 3A)
Relay
Wire Gauge:22-24AWG, Torque: 4Kgf-cm
Multi-function indication
output contact
Power for speed setting
Analog Voltage, current
frequency command
Multi-function assistant terminal
Common signal
Multi-function input selection 1
Multi-function input selection 2
Multi-function input selection 3
VR
Figure 4 for models: VFD004L21D, VFD004L21E, VFD007L21D, VFD007L21E
Wiring Notes: PLEASE READ PRIOR TO INSTALLATION.
¾ Do not connect the AC input to any of the U/T1, V/T2, W/T3
terminals, as it will damage the AC drive..
¾ Ensure all screws are tightened to the proper torque rating.
1. During installation, follow all national and local electrical, construction,
and safety codes for the country the drive is to be installed in.
2. Ensure the appropriate protective devices (circuit breaker or fuses) are
connected between the power supply and AC drive.
3. Make sure that the leads are connected correctly and the AC drive is
properly grounded. (Ground resistance should not exceed 0.1
Ω
.)
4. Use ground leads that comply with AWG/MCM standards and keep
them as short as possible.
5. Multiple VFD-L units can be installed in one location. All the units should
be grounded directly to a common ground terminal. The VFD-L ground
terminals may also be connected in parallel, as shown in the figure
below. Ensure there are no ground loops.
Forward
running
6. When the AC drive output terminals U/T1, V/T2, and W/T3 are
connected to the motor terminals U, V, and W, respectively, the motor
will rotate counterclockwise (as viewed from the shaft ends of the motor)
when a forward operation command is received. To reverse the
direction of motor rotation, switch over any of the two motor leads.
7. Make sure that the power is capable of supplying the correct voltage
and required current to the AC drive.
8. Do not attach or remove wiring when power is applied to the AC drive.
9. Do not monitor the signals on the circuit board while the AC drive is in
operation.
10. Route the power and control wires separately, or orthogonal to each
other.
11. If a filter is required for reducing EMI (Electro-Magnetic Interference),
install it as close as possible to AC drive. EMI can also be reduced by
lowering the Carrier Frequency.
12. If the AC drive is installed in the place where a load reactor is needed,
install the filter close to U/T1, V/T2, W/T3 side of AC drive. Do not use a
Capacitor or L-C Filter (Inductance-Capacitance) or R-C Filter
(Resistance-Capacitance).
13. When using a general GFCI (Ground Fault Circuit Interrupter), select a
current sensor with sensitivity of 200mA or above, and not less than
0.1-second operation time to avoid nuisance tripping. For the specific
GFCI of the AC motor drive, please select a current sensor with
sensitivity of 30mA or above.
4 Summary of Parameters
Group 0: User Parameters aThe parameter may be set during operation.
Pr. Functions Settings
Factory
Setting
0-00 Identity code of drive
(Read only)
d1: 40W
d2: 100W
d3: 200W
d4: 400W
d5: 750W
d6: 1.5KW
0-01 Rated current display
(Read only)
40W: d0.4A
100W: d0.8A
200W: d1.6A
400W: d2.5A
750W: d4.2A
1.5K: d7.0A
0-02 Parameter reset d10: Reset Parameters to Factory Setting d0
a0-03 Start-up display of AC
drive
d0: F (Frequency command)
d1: H (output frequency)
d2: U (user-defined unit)
d3: A (output current)
d0
a0-04 User-defined Unit d0: Display User-Defined Unit (u)
d1: Display Counter Value (C)
d2: Display Process Operation (1=tt)
(Display the current speed’s step and the
rest time for this step speed)
d3: Display DC-BUS voltage (U)
d4: Display output voltage (E)
d0
a0-05 User-defined
coefficient K
d0.1 ~ d160
d1.0
0-06 Software version Read only #.#
0-07 Password input d0 ~ d999 d0
0-08
Password
configuration
d0 ~ d999 d0
Group 1: Basic Parameters
Pr. Functions Settings
Factory
Setting
1-00 Maximum operation Freq. d50.0 ~ d400Hz d60.0
1-01 Maximum setting Freq. d10.0 ~ d400Hz d60.0
1-02 Maximum output voltage d2.0 ~ d255V d220
1-03 Mid-point freq. d1.0 ~ d400Hz d1.0
1-04 Mid-point voltage d2.0 ~ d255V d12.0
1-05 Minimum output freq. d1.0 ~ d60.0Hz d1.0
1-06 Minimum output voltage d2.0 ~ d255V d12.0
1-07 Upper bound of freq. d1 ~ d110% d100
1-08 Lower bound of freq. d0 ~ d100% d0.0
a1-09 Accel time 1 (Tacc1) d0.1 ~ d600 Sec d10.0
a1-10 Decel time 1 (Tdec1) d0.1 ~ d600 Sec d10.0
a1-11 Accel time 2 d0.1 ~ d600 Sec d10.0
a1-12 Decel time 2 d0.1 ~ d600 Sec d10.0
a1-13 JOG Accel time d0.1 ~ d600 Sec d10.0
a1-14 JOG Decel time d0.0 ~ d600 Sec d10.0
a1-15 JOG frequency d1.0Hz~d400Hz d6.0
1-16 Auto-accel/decel d0: Linear Accel/Decel
d1: Auto accel, linear decel
d2: Linear accel, auto decel,
d3: Auto Accel/Decel
d4: Linear accel. Auto decel, stall
prevention during
deceleration
d5: Auto accel. Auto decel, stall
prevention during
deceleration
d0
1-17
S-curve setting in
acceleration
d0 ~ d7 d0
1-18
S-curve setting in
deceleration
d0 ~ d7 d0
Group 2: Operation Method Parameters
Pr. Functions Settings
Factory
Setting
2-00 Source of frequency
command
d0: Digital keypad
d1: 0 ~ 10V from AVI
d2: 4 ~ 20mA from AVI
d3: Controlled by V.R on drive
d4: RS-485 communication interface
d0
2-01 Source of operation
command
d0: By digital keypad
d1: By external terminals, keypad STOP
enable
d2: By external terminals, keypad
d3 : By RS-485 communication interface, keypad
STOP enable
d4 : By RS-485 communication interface, keypad
STOP disable
d0
2-02 Stop method
d0: Ramp stop d1: Coast stop
d0
2-03 Carrier freq.
d3 ~d10K Hz
d10

Other manuals for Delta VFD-L Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD-L Series and is the answer not in the manual?

Delta VFD-L Series Specifications

General IconGeneral
BrandDelta
ModelVFD-L Series
CategoryController
LanguageEnglish

Related product manuals