Chapter 11 Description of Parameter Settings|C200 Series
11-2
input the password set in Pr.00-07 to reset to factory settings.
When it is set to 5, KWH display value can be reset to 0 even when the drive is operating. Pr.
05-26, 05-27, 05-28, 05-29, 05-30 reset to 0.
When it is set to 6: clear internal PLC program
When it is set to 7: reset the related settings of CANopen slave.
Start-up Display Selection
Factory setting: 0
Settings 0: Display the frequency command (F)
1: Display the actual output frequency (H)
2: Display User define (U)
3: Output current ( A)
This parameter determines the start-up display page after power is applied to the drive. User
defined choice display according to the setting in Pr.00-04.
Content of Multi-function Display
Factory setting: 3
Settings
0: Display output current (A)
1: Display counter value (c)
2: Display actual output frequency (H.)
3: Display DC-BUS voltage (v)
4: Display output voltage (E)
5: Display output power angle (n)
6: Display output power in kW (P)
7: Display actual motor speed rpm (r = 00: positive speed; -00 negative
speed)
8: Display estimate output torque % (t = 00: positive torque; -00 negative
torque) (t) (refer to Note 4)
9: Reserved
10: Display PID feedback in % (b)
11: Display AVI in % (1.), 0~10V/4-20mA/0-20mA corresponds to 0~100%
(Refer to Note 1)
12: Display ACI in % (2.), 4~20mA/0~10V/0-20mA corresponds to
0~100%Refer to Note 1
13: Display AUI in % (3.), -10V~10V corresponds to -100~100%(Refer to
Note 2)
14: Display the temperature of IGBT in oC (i.)
15: Display the temperature of capacitance in oC (c.)
16: The status of digital input (ON/OFF) refer to Pr.02-12 (i) (Refer to Note
2)
17: Display digital output status ON/OFF (Pr.02-18) (o) (Refer to NOTE 3)
18: Display the multi-step speed that is executing (S)
19: The corresponding CPU pin status of digital input (d) (refer to NOTE 2)