Chapter 11 Description of Parameter Settings|C200 Series
11-25
Pr.01-12~01-19. If the accel./decel. time is too short, the actual accel./decel. time is greater than
the setting of accel./decel. time.
1
2
01-00
01-12 01-14
01-16
01-18
01-13
01-15
01-17 01-19
1
2
When Pr.01-44 is set to 0.
Frequency
Max.
Frequency
01-07
Min.
Frequency
accel. time
Time
decel. time
Accel./Decel. Time
When Pr.01-44 is set to 3.
Time Unit for Acceleration/Deceleration and S Curve
Factory Setting: 0
Settings 0: Unit 0.01 sec
1: Unit 0.1 sec
Time for CANopen Quick Stop
Factory Setting: 1.00
Settings
Pr. 01-45=0: 0.00~600.00 sec
Pr. 01-45=1: 0.0~6000.0 sec
It is used to set the time that decelerates from the max. operation frequency (Pr.01-00) to 0.00Hz in
CANopen control