Chapter 11 Description of Parameter Settings|C200 Series
11-76
Stator Resistance (Rs) of Induction Motor 2
Rotor Resistance (Rr) of Induction Motor 2
Factory Setting: #.###
Settings 0~65.535
Magnetizing Inductance (Lm) of Induction Motor 2
Stator Inductance (Lx) of Induction Motor 2
Factory Setting: #.#
Settings 0~6553.5 mH
Induction Motor 1/ 2 Selection
Factory Setting: 1
Settings 1: Motor 1
2: Motor 2
It is used to set the motor that driven by the AC motor drive.
Frequency for Y-connection/-connection Switch of Induction Motor
Factory Setting: 60.00
Settings 0.00~600.00Hz
Y-connection/-connection Switch of Induction Motor IM
Factory Setting: 0
Settings 0: Disable
1: Enable
Delay Time for Y-connection/-connection Switch of Induction Motor
Factory Setting: 0.200
Settings 0.000~60.000 sec
P.05-23 and Pr.05-25 are applied in the wide range motors and the motor coil will execute the
switch of Y-connection/Δ-connection as required. (The wide range motors has relation with the
motor design. In general, it has higher torque at low speed and Y-connection and it has higher
speed at high speed and connection. 
Pr.05-24 is used to enable/disable Y-connection/Δ-connection Switch.
When Pr.05-24 is set to 1, the drive will select by Pr.05-23 setting and current motor frequency to
switch motor to Y-connection or Δ-connection. At the same time, it will also affect motor
parameters.
Pr.05-25 is used to set the switch delay time of Y-connection/Δ-connection.
When output frequency reaches Y-connection/Δ-connection switch frequency, drive will delay by
Pr.05-25 before multi-function output terminals are active.