Chapter 14 PLC Function |C200 Series
14-30
Command code: Operation:
LD X0
Load contact A of
X0
OR X1
Connect to contact
A of X1 in parallel
OUT Y1
Drive Y1 coil
Example
Ladder diagram:
X0
X1
Y1
Mnemonic Function
ORI Parallel connection- B contact
X0~X17 Y0~Y17 M0~M799 T0~159 C0~C79 D0~D399
Operand
9 9 9 9 9
The ORI command is used in the parallel connection of B contact. The function of the
command is to readout the status of present specific series connection contacts, and
then to perform the “OR” calculations with the logic calculation result before the
contacts, thereafter, saving the result into the accumulative register.
Command code: Operation:
LD X0
Load contact A of X0
ORI X1
Connect to contact B of
X1 in parallel
OUT Y1
Drive Y1 coil
Example
Ladder diagram:
X0
X1
Y1
Mnemonic Function
ANB Series connection (Multiple Circuits)
Operand None
To perform the “ANB” calculation between the previous reserved logic results and
contents of the accumulative register.
Command code: Operation:
LD X0 Load contact A of X0
ORI X2
Connect to contact B of
X2 in parallel
LDI X1
Load contact B of X1
OR X3
Connect to contact A of
X3 in parallel
ANB
Connect circuit block in
series
Example
Ladder diagram:
X1
X3
Y1
X0
X2
ANB
Block A
Block B
OUT Y1
Drive Y1 coil
Mnemonic Function
ORB Parallel connection (Multiple circuits)
Operand None
ORB is to perform the “OR” calculation between the previous reserved logic results
and contents of the accumulative register.