Chapter 10 Summary of Parameter Settings|C200 Series
10-2
Parameter Explanation
Settings
Factory
Setting
14: Display the temperature of IGBT in oC (i.)
15: Display the temperature of capacitance in oC
(c.)
16: The status of digital input (ON/OFF) (i)
17: The status of digital output (ON/OFF) (o)
18: Multi-step speed (S)
19: The corresponding CPU pin status of digital
input (d.)
20: The corresponding CPU pin status of digital
output (0.)
21~24:
Reserved
25: Overload count (0.00~100.00%) (h.)
26: Ground Fault GFF (Unit :%)(G.)
27: DC Bus voltage ripple (Unit: Vdc) (r.)
28: Display PLC data D1043 (C)
29: Reserved
30: Display output of user defined (U)
31: Display Pr.00-05 user Gain(K)
32~34: Reserved
35: Control Mode display: 0= Speed control mode
(SPD), 1= torque control mode (TQR) (t.)
36: Present operating carrier frequency of drive
(Hz) (J.)
00-05
Coefficient Gain in Actual
Output Frequency
0~160.00
0
00-06 Software Version
Read-only
#.#
00-07
Parameter Protection
Password Input
065535
0~3: the times of password attempts
0
00-08
Parameter Protection
Password Setting
0 ~ 65535
0: No password protection / password is entered
correctly (Pr00-07)
1: Parameter is locked
0
00-09
Reserved
00-10 Control Mode
0: Speed mode
1: Reserved
2: Torque mode
0
00-11 Control of Speed Mode
0: VF (IM V/f control)
1: VFPG (IM V/f control+ Encoder)
2: SVC(IM Sensorless vector control)
3: FOCPG (IM FOC vector control+ encoder)
4: Reserved
5: Reserved
6: PM Sensorless (PM field oriented sensorless
vector control)
0
00-12 Reserved
00-13 Torque Mode Control
0: TQCPGIM Torque control + Encoder
1: Reserved
2: Reserved
0
00-14
Reserved
00-15
Reserved
00-16 Load Selection
0: Normal load
1: Heavy load
0
Normal load: 1-15HP 8
00-17 Carrier Frequency
Heavy load: 1-15HP 2
00-18 Single or Three-phase setting
0: 3-phase
1: 1-phase
Read