Chapter 10 Summary of Parameter Settings|C200 Series
10-11
03 Analog Input/Output Parameters
Parameter Explanation Settings
Factory
Setting
03-00
Analog Input Selection
(AVI)
0: No function 1
03-01
Analog Input Selection
(ACI)
1: Frequency command (torque limit under torque
control mode)
0
03-02
Analog Input Selection
(AUI)
2: Torque command (torque limit under speed mode) 0
3: Torque compensation command
4: PID target value
5: PID feedback signal
6: PTC thermistor input value
7: Positive torque limit
8: Negative torque limit
9: Regenerative torque limit
10: Positive/negative torque limit
03-03 Analog Input Bias (AVI) -100.0~100.0% 0
03-04 Analog Input Bias (ACI) -100.0~100.0% 0
03-05
Analog Positive Voltage
Input Bias (AUI)
-100.0~100.0% 0
03-06 Reserved
03-07
Positive/negative Bias
Mode (AVI)
03-08
Positive/negative Bias
Mode (ACI)
03-09
Positive/negative Bias
Mode (AUI)
0: No bias
1: Lower than or equal to bias
2: Greater than or equal to bias
3: The absolute value of the bias voltage while serving
as the center
4: Serve bias as the center
0
03-10
Analog Frequency
Command for Reverse
Run
0: Negative frequency is not valid. Forward and
reverse run is controlled by digital keypad or
external terminal.
1: Neagtive frequency is valid. Positive frequency =
forward run; negative frequency = reverse run.
Direction can not be switched by digital keypad or
external teriminal control.
0
03-11 Analog Input Gain (AVI) -500.0~500.0% 100.0
03-12 Analog Input Gain (ACI) -500.0~500.0% 100.0
03-13
Analog Positive Input
Gain (AUI)
-500.0~500.0% 100.0
03-14
Analog Negative Input
Gain (AUI)
-500.0~500.0% 100.0
03-15
Analog Input Filter Time
(AVI)
0.00~20.00 sec. 0.01
03-16
Analog Input Filter Time
(ACI)
0.00~20.00 sec. 0.01
03-17
Analog Input Filter Time
(AUI)
0.00~20.00 sec. 0.01
03-18
Addition Function of the
Analog Input
0: Disable (AVI, ACI, AUI)
1: Enable
0
03-19 ACI Signal Loss
0: Disable
1: Continue operation at the last frequency
2: Decelerate to 0Hz
3: Stop immediately and display ACE
0
03-20
Multi-function Output 1
(AFM1)
0: Output frequency (Hz) 0