Chapter 11 Description of Parameter Settings|C200 Series
11-5
00-08
00-07
Decode Flow Chart
Password Set
Password Input
Pr.00-08=0
Yes
No
Shut down th drive
and re-apply power
Re-apply power.
(The password is still valid)
Reserved
Control Mode
Factory Setting: 0
Settings 0: Speed mode
1: Reserved
2: Torque mode
This parameter determines the control mode of C200 series AC motor drive.
Control of Speed Mode
Factory Setting: 0
Settings 0: VF (IM V/f control)
1: VFPG (IM V/f control+ Encoder)
2: SVC(IM sensorless vector control)
3: FOCPG (IM FOC vector control+ encoder)
4~5: Reserved
6 : PM Sensorless (PM field oriented sensorless vector control)
This parameter determines the control method of the AC motor drive:
0: (IM V/f control): user can design proportion of V/f as required and can control multiple motors
simultaneously.
1: (IM V/f control + Encoder): user can use optional PG card with encoder for the closed-loop
speed control.
2: (IM Sensorless vector control): get the optimal control by the auto-tuning of motor
parameters.
3: (IM FOC vector control+ encoder): besides torque increases, the speed control will be more
accurate (1:1000).
6: PM Sensorless (PM field oriented sensorless vector control)