Chapter 11 Description of Parameter Settings|C200 Series
11-21
01-00
01-13,15,17,19,21
01-12,14,16,18,20
Frequency
Time
Max. Output
Frequency
Frequency
Setting
accel. time decel. time
Accel./Decel. Time
JOG Frequency
Factory Setting: 6.00
Settings 0.00~600.00Hz
Both external terminal JOG and key “F1” on the keypad KPC-CC01 can be used. When the jog
command is ON, the AC motor drive will accelerate from 0Hz to jog frequency (Pr.01-22). When the
jog command is OFF, the AC motor drive will decelerate from Jog Frequency to zero. The Jog
Accel./Decel. time (Pr.01-20, Pr.01-21) is the time that accelerates from 0.0Hz to Pr.01-22 JOG
Frequency.
The JOG command can’t be executed when the AC motor drive is running. In the same way, when
the JOG command is executing, other operation commands are invalid except forward/reverse
commands and STOP key on the digital keypad.
It does not support JOG function in the optional keypad KPC-CE01.
1st/4th Accel./decel. Frequency
Factory Setting: 0.00
Settings 0.00~600.00Hz
The transition from acceleration/deceleration time 1 to acceleration/deceleration time 4, may also
be enabled by the external terminals. The external terminal has priority over Pr. 01-23.
Freque nc
y
Ti me
01-23
4th Acceleration
Time
4th Deceleration
Time
1st Acceler ati on
Time
1st Deceleration
Time
1st/4th Acceleration/Deceleration Frequency Switching
S-curve Acceleration Begin Time 1
S-curve Acceleration Arrival Time 2
S-curve Deceleration Begin Time 1