Chapter 10 Summary of Parameter Settings|C200 Series
10-16
05 Motor Parameters
Parameter Explanation Settings
Factory
Setting
05-00 Motor Auto Tuning
0: No function
1: Rolling test for induction motor(IM) (Rs, Rr, Lm, Lx,
no-load current)
2: Static test for induction motor(IM)
3: No function
4: Rolling test for PM motor magnetic pole
5: Rolling test for PM motor
6: Rolling test for IM motor flux curve
12: FOC Sensorless inertia estimation
13: High frequency and blocked rotor test for PM motor
0
05-01
Full-load Current of
Induction Motor 1(A)
10~120% of drive’s rated current
#.##
05-02
Rated Power of Induction
Motor 1(kW)
0~655.35kW
#.##
05-03
Rated Speed of Induction
Motor 1 (rpm)
0~65535
1710(60Hz 4poles) ; 1410(50Hz 4 poles)
1710
05-04
Pole Number of Induction
Motor 1
2~20
4
05-05
No-load Current of
Induction Motor 1 (A)
0~ Pr.05-01 factory setting
#.##
05-06
Stator Resistance (Rs) of
Induction Motor 1
0~65.535mΩ
0
05-07
Rotor Resistance (Rr) of
Induction Motor 1
0~65.535mΩ
0
05-08
Magnetizing Inductance
(Lm) of Induction Motor 1
0~6553.5mH
0
05-09
Stator Inductance (Lx) of
Induction Motor 1
0~6553.5mH
0
05-10 ~
05-12
Reserved
05-13
Full-load Current of
Induction Motor 2 (A)
10~120%
#.##
05-14
Rated Power of Induction
Motor 2 (kW)
0~655.35kW
#.##
05-15
Rated Speed of Induction
Motor 2 (rpm)
0~65535
1710(60Hz 4 poles) ; 1410(50Hz 4 poles)
1710
05-16
Pole Number of Induction
Motor 2
2~20
4
05-17
No-load Current of
Induction Motor 2 (A)
0~ Pr.05-01 factory setting
#.##
05-18
Stator Resistance (Rs) of
Induction Motor 2
0~65.535mΩ
0
05-19
Rotor Resistance (Rr) of
Induction Motor 2
0~65.535mΩ
0
05-20
Magnetizing Inductance
(Lm) of Induction Motor 2
0~6553.5mH
0
05-21
Stator Inductance (Lx) of
Induction Motor 2
0~6553.5mH
0
05-22
Induction Motor 1/ 2
Selection
1: motor 1
2: motor 2
1
05-23
Frequency for
Y-connection/-connectio
n Switch of Induction
Motor
0.00~600.00Hz
60.00
05-24
Y-connection/-connectio
n Switch of Induction
Motor
0: Disable
1: Enable 0
05-25
Delay Time for
Y-connection/-connectio
n Switch of Induction
0.000~60.000 sec.
0.200