Chapter 11 Description of Parameter Settings|C200 Series
11-18
(3) High starting torque
60.0
01-00
01-01
01-02
01-03
01-05
01-04
01-06
01-07
01-08
60.0
220.0
3.00
23.0
1.50
18.0
50.0
01-00
01-01
01-02
01-03
01-05
01-04
01-06
01-07
01-08
50.0
220.0
2.20
23.0
1.30
14.0
Motor spec. 60Hz
Motor spec. 50Hz
Pr. Setting
Pr.
Setting
V
F
220
18
1.5
60.0
23
3
V
F
220
14
1.3
50.0
23
2.2
Start-Up Frequency
Factory Setting: 0.50
Settings 0.0~600.00Hz
๎ When start frequency is higher than the min. output frequency, drivesโ output will be from start
frequency to the setting frequency. Please refer to the following diagram for details.
๎ Fcmd=frequency command,
Fstart=start frequency (Pr.01-09),
fstart=actual start frequency of drive,
Fmin=4th output frequency setting (Pr.01-07/Pr.01-41),
Flow=output frequency lower limit (Pr.01-11)
Fcmd>Fmin
Fstart>Fmin
NO
YES
YES
fstart=Fstart
NO
fstart=Fmin
Flow=0
Flow=0
YES
H=Fcmd
YES
H=Fcmd
NO
Fcmd>Flow
YES
Fcmd>Fmin
YES
H=Fcmd
NO
NO
Fcmd<Fmin
NO
H=Flow
YES
NO
Fcmd
Fmin
Fstart
Fcmd
Fmin
Fstart
Fcmd1>Flow &
Fcmd1>Fmin
Fmin
Flow
Fcmd2>Flow &
Fcmd2<Fmin
Flow>Fcmd1
>Fmin
Fmin
Flow
Fmin>Fcmd2
60Hz
60Hz
Hz
Time
Hz
Time
Time
Time
Hz
Hz
Fcmd1
Fcmd2
H=Flow
Fcmd1
Fcmd2
H=Fc m d 1
by Pr.01-34
by
Pr.01-34
by
Pr.01-34
by Pr.01-34
by Pr.01-34
operation after
start-up