EasyManua.ls Logo

Delta VFD015CB43A-20 - 03 Analog Input;Output Parameters

Delta VFD015CB43A-20
363 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 11 Description of Parameter Settings|C200 Series
11-44
03 Analog Input/Output Parameter This parameter can be set during operation.
Analog Input Selection (AVI)
Factory Setting: 1
Analog Input Selection (ACI)
Factory Setting: 0
Analog Input Selection (AUI)
Factory Setting: 0
Settings
0: No function
1: Frequency command (torque limit under torque control mode)
2: Torque command (torque limit under speed mode)
3: Torque compensation command
4: PID target value
5: PID feedback signal
6: PTC thermistor input value
7: Positive torque limit
8: Negative torque limit
9: Regenerative torque limit
10: Positive/negative torque limit
When it is frequency command or TQC speed limit, the corresponding value for 0~±10V/4~20mA is
0 – max. output frequency(Pr.01-00)
When it is torque command or torque limit, the corresponding value for 0~±10V/4~20mA is 0 – max.
output torque (Pr.11-27).
When it is torque compensation, the corresponding value for 0~±10V/4~20mA is 0 rated torque.
Positive torque
Reverse
03-00~02=7
Positive torque limit
03-00~02=8
Negative torque limit
03-00~02=9
Regenerative
torque limit
03-00~02=10
Positive/negative torque limit
Negative Torque
Forward
03-00~02=10
Positive/negative torque limit
03-00~02=9
Regenerative
torque limit
Analog Input Bias (AVI)
Factory Setting: 0
Settings -100.0~100.0%
It is used to set the corresponding AVI voltage of the external analog input 0.