Chapter 11 Description of Parameter Settings|C200 Series
11-72
05 Motor Parameters This parameter can be set during operation.
Motor Auto Tuning
Factory Setting: 0
Settings 0: No function
1: Rolling test for induction motor (Rs, Rr, Lm, Lx, no-load current)
2: Rolling test for induction motor
4: Rolling test for PM motor magnetic pole
5: Rolling test for PM motor
6: Rolling test for IM motor flux curve
12: FOC Sensorless inertia estimation
13: High frequency and blocked rotor test for PM motor parameter
Induction Motor
Press [Run]to beging auto tuning. The measured value will be written into motor 1 (Pr.05-05 ~05-09,
Rs, Rr, Lm, Lx, no-load current) and motor 2 (Pr.05-17 to Pr.05-21) automatically.
To begin AUTO-Tuning in rolling test:
1. Make sure that all the parameters are set to factory settings and the motor wiring is correct.
2. Make sure the motor has no-load before executing auto-tuning and the shaft is not connected
to any belt or gear motor. It is recommended to set to 2 if the motor can’t separate from the
load.
3.
Motor 1 Parameter Motor 2 Parameter
Motor Rated Frequency
01-01 01-35
Motor Rated Voltage
01-02 01-36
Motor Full-load Current
05-01 05-13
Motor Rated Power
05-02 05-14
Motor Rated Speed
05-03 05-15
Motor Pole Numbers
05-04 05-16
4. Set Pr.05-00=1 and press [Run], the drive will begin auto-tuning. Please be aware of the motor
that it starts spinning as [Run] is pressed.
5. When auto-tuning is completed, please check if the measured values are written into motor 1
(Pr.05-05 ~05-09) and motor 2 (Pr.05-17 ~05-21) automatically.
6. Mechanical equivalent circuit
V
S
I
Rs
Rr
Lx
Lm
Pr.0 5- 06
Pr.0 5- 18
Pr.05-09
Pr.05-21
Pr.0 5- 08
Pr.0 5- 20
Pr.0 5- 07
Pr.0 5- 19
If Pr.05-00 is set to 2 (static test), user needs to input the no-load current value of motor
into Pr.05-05 for motor 1/Pr.05-17 for motor 2.