Chapter 11 Description of Parameter Settings|C200 Series
11-75
Factory Setting: #.###
Settings 0~65.535
Magnetizing Inductance(Lm) of Induction Motor 1
Stator inductance(Lx) of Induction Motor 1
Factory Setting: #.#
Settings 0~6553.5mH
~
Reserved
Full-load Current of Induction Motor 2A
Unit: Ampere
Factory Setting:#.##
Settings 10~120%
This value should be set according to the rated frequency of the motor as indicated on the motor
nameplate. The factory setting is 90% X rated current.
Example: The rated current for 7.5HP (5.5kW) is 25A and factory setting is 22.5A. The range for
setting will be 10~30A.(25*40%=10A and 25*120%=30A)
Rated Power of Induction Motor 2 (kW)
Factory Setting: #.##
Settings 0~655.35 kW
It is used to set rated power of the motor 2. The factory setting is the power of the drive.
Rated Speed of Induction Motor 2 (rpm)
Factory Setting: 1710
Settings 0~65535
It is used to set the rated speed of the motor and need to set according to the value indicated on
the motor nameplate.
Pole Number of Induction Motor 2
Factory Setting: 4
Settings 2~20
It is used to set the number of motor poles (must be an even number).
No-load Current of Induction Motor 2 (A)
Unit: Ampere
Factory Setting: #.##
Settings 0 to the factory setting in Pr.05-01
The factory setting is 40% X rated current.