Chapter 11 Description of Parameter Settings|C200 Series
11-96
230V
Pr.06-55=1
Pr.06-55=0 or 2
(50℃: UL open-type)
(40℃:UL type1 or open type_size by size)
100
110
90
80
70
50
2 56789101112131415
Fc
(kHz)
ti
(
)
VFD004~037CB23A
VFD004~022CB21A
60
40
4
3
230V
Pr.06-55=0 or 2
(40℃: UL open-type)
(30℃: UL type1 or open type_size by size)
100
110
90
80
70
50
2 56789101112131415
Fc
(kHz)
ti
(
)
VFD004~037CB23A
VFD004~022CB21A
60
40
4
3
NOTE
※ The mounting clearances stated in the figure is for installing the drive in
an open area. To install the drive in a confined space (such as cabinet
or electric box), please follow the following three rules: (1) Keep the
minimum mounting clearances. (2) Install a ventilation equipment or an
air conditioner to keep surrounding temperature lower than operation
temperature. (3) Refer to parameter setting and set up Pr. 00-16,
Pr.00-17, and Pr. 06-55.
※ The following table shows heat dissipation and the required air volume
when installing a single drive in a confined space. When installing
multiple drives, the required air volume shall be multiplied by the
number the drives.
※ Refer to the chart (Air flow rate for cooling) for ventilation equipment
design and selection.
※ Refer to the chart (Power dissipation) for air conditioner design and
selection.
Minimum mounting clearances:
Frame A (mm) B (mm) C (mm) D (mm)
A~C 60 30 10 0
Air flow rate for cooling Power Dissipation
Model No.
Flow Rate
(cfm)
Flow Rate
(m
3
/hr)
Loss External
(Heat sink)
Internal Tota l
VFD004CB21A-20/-21/-21M
- -
16 20 36
VFD007CB21A-20/-21/-21M
- -
32 39 72
VFD015CB21A-20/-21/-21M 15 26 60 52 112
VFD022CB21A-20/-21/-21M 15 26 85 69 154
VFD004CB23A-20/-21/-21M
- -
21 17 37
VFD007CB23A-20/-21/-21M
- -
35 26 61
VFD015CB23A-20/-21/-21M 15 26 56 32 89
VFD022CB23A-20/-21/-21M 15 26 82 34 116
VFD037CB23A-20/-21/-21M 15 26 118 43 161
VFD007CB43A-20/-21/-21M - - 35 24 59
VFD015CB43A-20/-21/-21M - - 47 27 74
VFD022CB43A-20/-21/-21M 15 26 75 30 105
VFD037CB43A-20/-21/-21M 15 26 110 33 143
VFD040CB43A-20/-21/-21M 15 26 126 34 160
VFD055CB43A-20/-21/-21M 15 26 145 37 181
VFD075CB43A-20/-21/-21M 24 41 212 83 295
※ The required airflow shown in chart is for installing one
※ The heat dissipation shown in the chart is for