Chapter 14 PLC Function |C200 Series
14-26
14.5.4 Communication Address for PLC Devices
Device Range Type Address (Hex)
X 00~17 (Octal) bit 0400~040F
Y 00~17 (Octal) bit 0500~050F
T 00~159 bit/word 0600~069F
M 000~799 bit 0800~0B1F
M 1000~1079 bit 0BE8~0C37
C 0~79 bit/word 0E00~0E47
D 00~399 word 1000~118F
D 1000~1099 word 13E8~144B
Function Code
Function Code
Description Supported Devices
01
Read coil status
Y, M, T, C
02
Read input status
X,Y,M,T,C
03
Read one data
T,C,D
05
Force changing one coil status
Y, M , T, C
06
Write in one data
T,C,D
0F
Force changing multiple coil
status
Y, M , T, C
10
Write in multiple data
T,C,D
Only when PLC is at Stop status, PLC data can be read/write via communication device. When PLC
is at Run status, the communication address should be the mapping address, e.g. for Pr.04-00 it
maps to 0400H.
NOTE
When PLC function is activated, C2000 can Read/Write the PLC and drives parameter by different addresses (pre-defined
station number for the AC motor drive is 1, for PLC station number is 2)