Chapter 11 Summary of Parameter SettingsC2000 Plus
11-19
Pr. Parameter Name Setting Range Default
02-33
Output Current Level Setting for Multi-
Function Output Terminal
0–100% 0
02-34
Output Frequency Setting for Multi-
Function Output Terminal
0.00–599.00 Hz
(Motor speed when using PG Card)
3.00
02-35
External Operation Control Selection
after Reset and Reboot
0: Disabled
1: Drive runs if the RUN command remains after
reset or reboot
0
02-47 Motor Zero-Speed Level 0–65535 rpm 0
02-48
Maximum Frequency of Resolution
Switch
0.00–599.00 Hz
60.00
02-49
Switch Delay Time of Maximum
Output Frequency
0.000–65.000 sec. 0.000
02-50
Display the Status of Multi-Function
Input Terminal
Monitor the status of multi-function input terminals
Read
only
02-51
Display the Status of Multi-Function
Output Terminal
Monitor the status of multi-function output
terminals
Read
only
02-52
Display the External Multi-Function
Input Terminals Used by PLC
Monitor the status of PLC input terminals
Read
only
02-53
Display the External Multi-Function
Output Terminals Used by PLC
Monitor the status of PLC output terminals
Read
only
02-54
Display the Frequency Command
Executed by External Terminal
0.00–599.00 Hz (Read only)
Read
only
02-56 Brake Release Check Time 0.000–65.000 sec. 0.000
02-57
Multi-Function Output Terminal
(Function 42): Brake Current Check
Point
0–100% 0
02-58
Multi-Function Output Terminal
(Function 42): Brake Frequency
Check Point
0.00–599.00 Hz 0.00
02-63
Frequency Reached Detection
Amplitude
0.00–599.00 Hz 0.00
02-70 IO Card Types
1: EMC-BPS01
4: EMC-D611A
5: EMC-D42A
6: EMC-R6AA
11: EMC-A22A
Read
only
02-71 DFM Output Selection
0: Use frequency with speed control as DFM
output frequency
1: Use frequency with system acceleration /
deceleration as DFM output frequency
0