Chapter 12 Descriptions of Parameter SettingsC2000 Plus
12.1-02-5
Settings Functions Descriptions
7
Acceleration /
deceleration speed
inhibit
When you enable this function, the drive stops acceleration or
deceleration immediately. After you disable this function, the AC
motor drive starts to accelerate or decelerate from the inhibit
point.
8
1
st
and 2
nd
acceleration /
deceleration time
selection
You can select the acceleration and deceleration time of the drive
with this function, or from the digital status of the terminals; there
are four acceleration and deceleration selections.
9
3
rd
and 4
th
acceleration /
deceleration time
selection
10
External Fault (EF) Input
(Pr.07-20)
For external fault input, the drive decelerates according to the
Pr.07-20 setting, and the keypad shows “EF” (it shows the fault
record when an external fault occurs). The drive keeps running
until the fault is cleared
(terminal status restored) after RESET.
11
Base block (B.B.) input
from external
ON: the output of the drive stops immediately. The motor is in free
run and the keypad displays the B.B. signal. Refer to Pr.07-08 for
details.
12 Output voltage stops
ON: the output of the drive stops immediately and the motor is in
free run status. The drive is in output waiting status until
the
switch is turned to OFF, and then the drive restarts and runs to
the current setting frequency.