Chapter 12 Descriptions of Parameter SettingsC2000 Plus
12.1-02-29
Example:
When Pr.02-51 displays 0023h (hex) (that is, the value is 100011 (binary)), it means that RY1,
RY2, and MO1 are ON.
02-52
Display the External Multi-Function Input Terminals Used by PLC
Default: Read only
Settings Monitor the status of PLC input terminals
Pr.02-52 displays the external multi-function input terminals that used by PLC.
Example:
When Pr.02-52 displays 0034h (hex) (that is, the value is 110100 (binary)), it means that MI1,
MI3 and MI4 are used by PLC.