Chapter 12 Descriptions of Parameter SettingsC2000 Plus
12.1-06-18
Fault Code
bit0 bit1 bit2 bit3 bit4 bit5 bit6
current Volt. OL SYS FBK EXI CE
185: Motor code error (MoTo)
187: Flux linkage observer failure (FobF)
188: Load estimation error (TLAT)
189: Inertia estimation error (JsAT)
190: Bandwidth estimation error (BWAT)
191: Positioning failure during estimation (ATPF)
192: Homing deviation is too large (HmOE)
193: Cleaning multi-turn data failure (CMTE)
195: ASR AT process is too short (ATTv)
06-29
PTC Detection Selection / PT100 Motion
Default: 0
Settings 0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: No warning
Set the operation mode of a drive after detecting PTC / PT100 / KTY84.
06-30
PTC Level / KTY84 Level
Default: 50.0
Settings 0.0–100.0%
When Pr.06-86=0, the setting range is 0.0–100.0, with unit %, and the default is 50.0%.
When Pr.06-86=1, the setting range is 0.0–150.0, with unit ºC, and the default is 125.0ºC
Sets AVI/ACI/AUI analog input function Pr.03-00–03-02 to 6 [thermistor (PTC) input value].
The AUI terminal does not support KTY84-130.
Use this to set the PTC / KTY84 level, the corresponding value for 100% is the analog input
maximum value.
When Pr.06-86 is set as KTY84, Pr.06-30 setting range and the unit changes automatically.
06-31
Frequency Command at Malfunction
Default: Read only
Settings 0.00–599.00 Hz
When a malfunction occurs, check the current frequency command. If it happens again, it
overwrites the previous record.
06-32
Output Frequency at Malfunction
Default: Read only
Settings 0.00–599.00 Hz
When a malfunction occurs, check the current output frequency. If it happens again, it overwrites
the previous record.