Chapter 12 Descriptions of Parameter SettingsC2000 Plus
12.1-06-19
06-33
Output Voltage at Malfunction
Default: Read only
Settings 0.0–6553.5 V
When a malfunction occurs, check the current output voltage. If it happens again, it overwrites the
previous record.
06-34
DC Bus Voltage at Malfunction
Default: Read only
Settings 0.0–6553.5 V
When a malfunction occurs, check the current DC bus voltage. If it happens again, it overwrites
the previous record.
06-35
Output Current at Malfunction
Default: Read only
Settings 0.0–6553.5 Amp
When a malfunction occurs, check the current output current. If it happens again, it overwrites the
previous record.
06-36
IGBT Temperature at Malfunction
Default: Read only
Settings -3276.7–3276.7°C
When a malfunction occurs, check the current IGBT temperature. If it happens again, it overwrites
the previous record.
06-37
Capacitance Temperature at Malfunction
Default: Read only
Settings -3276.7–3276.7°C
When a malfunction occurs, check the current capacitance temperature. If it happens again, it
overwrites the previous record.
06-38
Motor Speed at Malfunction
Default: Read only
Settings -32767–32767 rpm
When a malfunction occurs, check the current motor speed in rpm. If it happens again, it overwrites
the previous record.
06-39
Torque Command at Malfunction
Default: Read only
Settings -32767–32767%
When a malfunction occurs, check the current torque command. If it happens again, it overwrites
the previous record.