Chapter 13 Warning CodesC2000 Plus
13-61
ID No. Display on LCD Keypad Warning Name Description
70
ExCom ID fail (ECid)
Duplicate MAC ID error
Node address setting error
Action and Reset
Action condition
Duplicate setting of MAC ID
Node address setting error
Action time N/A
Warning setting parameter N/A
Reset method Correct the setting and cycle the power
Reset condition N/A
Record N/A
Cause Corrective Actions
The setting address exceeds the
range (063)
Check the address setting of the communication card (Pr.09-70)
The speed setting exceeds the
range
Standard: 0–2, non-standard: 0–7
The address is duplicated with
other nodes on the BUS
Reset the address