Chapter 13 Warning CodesC2000 Plus
ID No. Display on LCD Keypad Warning Name Description
94
Copy PLC: size error
(CPLS)
Copy PLC Capacity size error
Action and Reset
Action condition Software detection
Action time Immediately acts
Warning setting parameter N/A
Reset method Manual reset
Reset condition Directly resets
Record N/A
Cause Corrective Actions
The PLC copied to C2000 Plus
exceeds the allowable capacity
Check if the copied PLC program is for C2000 Plus
Use C2000 Plus PLC program with correct capacity