12 Descriptions of Parameter Settings | VFD-ED
After running, use these parameters with multifunction input terminal setting 40 (Enable drive function),
and multifunction output terminal setting 15 (motor-controlled magnetic contactor output). When the
multifunction output terminals are ON, the drive starts outputting after the delay time in Pr.02-31. When
the drive stops outputting, multifunction output terminals release after the delay time in Pr.02-32.
MPSCC (Motor Phase Short Circuit Contactor) Release Delay Time between
Drive and Motor
Control Mode
VF VFPG SVC FOCPG
FOCPM
Default: 0.200
Settings 0.010~65.000 sec.
MPSCC (Motor Phase Short Circuit Contactor) Contracting Delay Time
between Drive and Motor
Control Mode
VF VFPG SVC FOCPG
FOCPM
Default: 0.200
Settings 0.010~65.000 sec.