EasyManua.ls Logo

Delta VFD055ED43S

Delta VFD055ED43S
447 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4 Main Circuit Terminals | VFD-ED
Frame D
Figure 4-11
Model
Main Circuit Terminals
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3,
+1, +2/B1, -, B2
Terminal
Min. Wire
Gauge
Max. Wire
Gauge
Screw Size &
Tightening
Torque (±10%)
Min. Wire
Gauge
Max. Wire
Gauge
Screw Size &
Tightening
Torque (±10%)
VFD150ED23S
21.1 mm²
(4 AWG)
33.6 mm²
(2 AWG)
M6
50 kg-cm
(43.4 lb-in.)
(4.9 N-m)
16 mm²
(6 AWG)
33.6 mm²
(2 AWG)
M6
50 kg-cm
(43.4 lb-in.)
(4.9 N-m)
VFD300ED43S
VFD185ED23S
26.7 mm²
(3 AWG)
16 mm²
(6 AWG)
VFD220ED43S
13.3 mm²
(6 AWG)
13.3 mm²
(6 AWG)
VFD220ED23S
33.6 mm²
(2 AWG)
16 mm²
(6 AWG)
Table 4-4
NOTE:
For UL installation compliance, select copper wires with voltage rating of 600V and temperature
resistance of 75°C.
Choose terminal wire size as Figure 4-12 shows.
Use insulated heat shrink tubing that is resistant to at least 600V to comply with UL and CSA
regulations (600 V, YDPU2), as Figure 4-13 shows.
If you install at Ta 50°C environment, use copper wires with voltage rating of 600V and
temperature resistance of 75°C or 90°C.
If you install at Ta 50°C above environment, use copper wires with voltage rating of 600V and
temperature resistance of 90°C or above.
To be UL installation compliant, you must use copper wires when installing. The wire gauge is
based on temperature resistance of 75°C, in accordance with UL requirements and
recommendations. Do not reduce the wire gauge when using high-temperature resistant wire.
Figure 4-12 Figure 4-13

Table of Contents

Related product manuals