Chapter 11 Summary of Parameter SettingsME300
11-14
Pr. Explanation Settings Default
02-50
Display the status of
multi-function input
terminal
Monitor the status of multi-function input terminals Read only
02-51
Display the status of
multi-function output
terminal
Monitor the status of multi-function output terminals Read only
02-54
Display the Frequency
command executed by
external terminal
Read only Read only
02-58
Multi-function output
terminal (function 42):
brake frequency check
point
0.00–599.00 Hz 0.00
02-72
Level of Preheating DC
Current
0–100%
0
02-73
Preheating DC Current
Duty Cycle
0–100%
0
02-81
EF active when terminal
count value reached
0: Terminal count value reached, no EF displays
1: Terminal count value reached, EF is active
0
02-82
Initial Frequency
command (F) mode after
stop
0: Use current Frequency command
1: Use zero Frequency command
2: Refer to Pr.02-83 to setup
0
02-83
Initial Frequency
command (F) setting after
stop
0.00–599.0 Hz 60.00