A-22
 
Choose suitable motor cable and precautions 
Improper installation and choice of motor cable will affect the performance of EMI filter. Be sure to observe the 
following precautions when selecting motor cable. 
 
1.  Use the cable with shielding (double shielding is the best). 
2.  The shielding on both ends of the motor cable should be grounded with the minimum length and maximum 
contact area. 
3.  Remove any paint on metal saddle for good ground contact with the plate and shielding. 
Remove any paint on metal saddle for good ground contact with 
the plate and shielding. 
saddle
the plate with grounding
 
Figure 1 
 
 
 
Saddle on both ends 
 
Saddle on one end 
 
Figure 2   
The length of motor cable 
When motor is driven by an Hybrid drive of PWM type, the motor terminals will experience surge voltages easily due 
to components conversion of Hybrid drive and cable capacitance. When the motor cable is very long (especially for 
the 460V series), surge voltages may reduce insulation quality. To prevent this situation, please follow the rules 
below: 
 Use a motor with enhanced insulation. 
 Connect an output reactor (optional) to the output terminals of the Hybrid drive 
 The length of the cable between Hybrid drive and motor should be as short as possible (10 to 20 m or less) 
 For models 7.5hp and above: 
Insulation level of motor  1000V  1300V  1600V 
460VAC input voltage  66 ft (20m)  328 ft (100m)  1312 ft (400m)