Appendix A Optional Accessories 
 
A-23
230VAC input voltage  1312 ft (400m)  1312 ft (400m)  1312 ft (400m) 
 
 For models 5hp and less: 
Insulation level of motor  1000V  1300V  1600V 
460VAC input voltage  66 ft (20m)  165 ft (50m)  165 ft (50m) 
230VAC input voltage  328 ft (100m)  328 ft (100m)  328 ft (100m) 
NOTE
 
Never connect phase lead capacitors or surge absorbers to the output terminals of the Hybrid drive. 
 If the length is too long, the stray capacitance between cables will increase and may cause leakage current. It 
will activate the protection of over current, increase leakage current or not insure the correction of current 
display. The worst case is that Hybrid drive may damage. 
 If more than one motor is connected to the Hybrid drive, the total wiring length is the sum of the wiring length 
from Hybrid drive to each motor. 
 For the 460V series Hybrid drive, when an overload relay is installed between the drive and the motor to protect 
motor over heating, the connecting cable must be shorter than 50m. However, an overload relay malfunction 
may still occur. To prevent the malfunction, install an output reactor (optional) to the drive or lower the carrier 
frequency setting (Pr.00-17).   
NOTE
 
When a thermal O/L relay protected by motor is used between Hybrid drive and motor, it may malfunction 
(especially for 460V series), even if the length of motor cable is only 165 ft (50m) or less. To prevent it, please 
use AC reactor and/or lower the carrier frequency (Pr. 00-17 PWM carrier frequency).