Chapter 12 Descriptions of Parameter SettingsC2000 Plus 
 
12.1-06-5 
 
06-03 
Over-Current Stall Prevention during Acceleration 
 
 
   
 Default:  
 
 
Settings  230V / 460V models   
 
 
 
Heavy duty: 0–195% (100% corresponds to 
the rated current of the drive) 
150 
 
 
 
Super Heavy duty: 0–210% (100% 
corresponds to the rated 
current of the drive) 
150 
 
 
 
575V / 690V models 
 
 
 
 
Light duty: 0–125% (100% corresponds to 
the rated current of the drive) 
120 
 
 
 
Normal duty: 0–150% (100% corresponds to 
the rated current of the drive) 
120 
 
 
 
Heavy duty: 0–180% (100% corresponds to 
the rated current of the drive) 
150 
 100% corresponds to the rated current of the drive (Pr.00-01). 
 This parameter only works in VF, VFPG, and SVC control mode. 
 The default for Pr.06-03 and Pr.06-04 is 150%, and the maximum value is 200%. If the DC voltage 
is higher than the 700 V
DC
 (460V models) or 350 V
DC
 (230V models), the maximum value for Pr.06-
03 and Pr.06-04 is 180%. 
 If the motor load is too large or the drive’s acceleration time is too short, the output current of the 
drive may be too high during acceleration, and it may cause motor damage or trigger the drive’s 
protection functions (oL or oc). Use this parameter to prevent these situations. 
 During acceleration, the output current of the drive may increase abruptly and exceed the setting 
value of Pr.06-03. In this case, the drive stops accelerating and keeps the output frequency 
constant, and then continues to accelerate until the output current decreases.