Chapter 12 Descriptions of Parameter SettingsC2000 Plus 
 
12.1-06-6 
 Refer to Pr.06-16 for more details of stall level in flux weakening region. The protection curve is 
as follows: 
 
 When you enable the over-current stall prevention, the drive’s acceleration time is longer than the 
setting. 
 When the over-current stall prevention occurs because the motor capacity is too small or operates 
in the default, decrease the Pr.06-03 setting value. 
 If you encounter any problem with the acceleration time, refer to the following guides for 
troubleshooting. 
1.  Increase the acceleration time to a proper value. 
2.  Set Pr.01-44 Auto Acceleration and Auto-Deceleration Setting to 1, 3 or 4 (auto-
acceleration). 
3. Related parameters:  
  Pr.01-12, Pr.01-14, Pr.01-16, Pr.01-18 Acceleration Time 1–4 
  Pr.01-44 Auto Acceleration and Auto-Deceleration Setting 
  Pr.02-13–02-14 Multi-function Output 1 (Relay 1 and Relay 2) 
  Pr.02-16–02-17 Multi-function Output (MO1 and MO2) 
 
06-04 
Over-Current Stall Prevention during Operation 
 
 
   
 Default:  
 
 
Settings  230V / 460V models   
 
 
 
Heavy duty: 0–195% (100% corresponds to 
the rated current of the drive) 
150 
 
 
 
Super Heavy duty: 0–210% (100% 
corresponds to the rated 
current of the drive) 
120 
 
 
 
575V / 690V models 
 
 
 
 
Light duty: 0–125% (100% corresponds to 
the rated current of the drive) 
120 
 
 
 
Normal duty: 0–150% (100% corresponds to 
the rated current of the drive) 
150 
 100% corresponds to the rated current of the drive (Pr.00-01). 
 This parameter only works in VF, VFPG, and SVC control modes.