Chapter 12 Description of Parameter SettingsC2000-HS
12.1-02-17
Settings Functions Descriptions
42 Crane Function
Use this function with Pr. 02-32, Pr. 02-33, Pr. 02-34, Pr. 02-57
and Pr. 02-58.
Refer to the crane function examples below.
43
Actual motor speed
higher than Pr. 02-47
Active when motor actual speed is higher than Pr. 02-47.
44 Low current output This function needs to be used with Pr. 06-71–Pr. 06-73
45
UVW output
electromagnetic valve
switch
Use this function with external terminal input = 49 (drive enabled)
and external terminal output = 45 (electromagnetic valve
enabled), and then the electromagnetic valve is ON or OFF
according to the status of the drive.
46 Master dEb output
When dEb rises at the master, MO sends a dEb signal to the
slave. Output the message when the master triggers dEb. This
ensures that the slave also triggers dEb. Then slave follows the
deceleration time of the master to stop simultaneously with the
master.
47 Closed brake output
When the drive stops, and the frequency command < Pr. 02-34,
the contact of corresponding multi-function terminal is ON. The
contact is OFF when the brake delay time exceeds Pr. 02-32.
49
Homing action complete
output
Output when homing action is completed.