Chapter  13  Warning  CodesCP2000 
 
13-33
ID No.  Display on LCD Keypad  Warning Name  Description 
74 
 
ExCom no power 
(ECnP) 
There is no power supply on the DeviceNet 
Action and Reset 
Action level  There is no power supply on the DeviceNet 
Action time  Immediately acts 
Warning setting parameter  N/A 
Reset method  Re-power 
Reset condition  N/A 
Record  N/A 
Cause  Corrective Actions 
The drive detects that DeviceNet 
has no power 
Check if the cable and power is normal. If yes, return to the factory for repair. 
 
ID No.  Display on LCD Keypad  Warning Name  Description 
75 
 
ExCom factory defect 
(ECFF) 
Factory default setting error 
Action and Reset 
Action level  Factory default setting error 
Action time  Immediately acts 
Warning setting parameter  N/A 
Reset method  Cycle the power 
Reset condition  N/A 
Record  N/A 
Cause  Corrective Actions 
Factory default setting error  Use DCISoft to reset to the default value. 
 
ID No.  Display on LCD Keypad  Warning Name  Description 
76 
 
ExCom inner error 
(ECiF) 
Serious internal error 
Action and Reset 
Action level  Internal memory saving error 
Action time  Immediately acts 
Warning setting parameter  N/A 
Reset method  Cycle the power 
Reset condition  N/A 
Record  N/A 
Cause  Corrective Actions 
Noise interference 
Verify wiring  of  the  control circuit,  and  wiring/grounding  of  the  main  circuit  to 
prevent interference. 
Cycle the power. 
The memory is broken 
Reset to the default value and check if the error still exists. If yes, replace the 
communication card.