Chapter 13 Warning CodesCP2000 
 
13-34
ID No.  Display on LCD Keypad  Warning Name  Description 
77 
 
ExCom IO Net break 
(ECio) 
IO connection break off 
Action and Reset 
Action level  IO connection between the communication card and the master is broken off 
Action time  Immediately acts 
Warning setting parameter  N/A 
Reset method  Manual reset 
Reset condition  Immediately reset 
Record  N/A 
Cause  Corrective Actions 
The cable is loose  Re-install the cable 
Incorrect parameter setting for 
master communication 
Check the setting for master communication parameter 
 
ID No.  Display on LCD Keypad  Warning Name  Description 
78 
 
ExCom Parameter 
data error   
(ECPP) 
Profibus parameter data error 
Action and Reset 
Action level  N/A 
Action time  N/A 
Warning setting parameter  N/A 
Reset method  Manual reset 
Reset condition  Immediately reset 
Record  N/A 
Cause  Corrective Actions 
The GSD file is incorrect  Get the correct GSD file from the software 
 
ID No.  Display on LCD Keypad  Warning Name  Description 
79 
 
ExCom configuration 
data error   
(ECPi) 
Profibus configuration data error 
Action and Reset 
Action level  N/A 
Action time  N/A 
Warning setting parameter  N/A 
Reset method  Manual reset 
Reset condition  Immediately reset 
Record  N/A 
Cause  Corrective Actions 
The GSD file is incorrect  Get the correct GSD file from the software