EasyManua.ls Logo

Det-Tronics 505 - Page 19

Det-Tronics 505
25 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17 95-8472
APPENDIX B [Canadian Standards Association (CSA) Approval Description]
THE FOLLOWING ITEMS, FUNCTIONS AND OPTIONS DESCRIBE THE CSA APPROVAL.
MODEL 505 SERIES COMBUSTIBLE GAS TRANSMITTER
Explosion-proof for Class I, Division 1, Groups B, C, & D Hazardous Locations per CSA C22.2 #30.
Dust/ignition-proof for Class II, Division 1, Groups E, F, & G, Class III Hazardous Locations per CSA C22.2 #25.
(For use with Sensor Termination Box.)
Enclosure Rating NEMA/Type 4X per CSA C22.2 #94. (For use with Sensor Termination Box.)
Operating temperature limits are –40°C to +75°C (–40°F to +167°F).
Storage temperature limits are –55°C to +85°C (–67°F to +185°F).
Explosion-proof ambient temperature limits are –55°C to +125°C (–67°F to +257°F).
Relative humidity range is 5 to 95% RH.
Performance verified for 0 to 100% LFL methane-in-air atmospheres per CSA C22.2 #152. Accuracy: ±3% LFL
from 0 to 50% LFL, ±5% LFL from 51% to 100% LFL.
For use with 226365-118 through 226365-125 Sensor Termination Boxes.
For use with Model CGS Series Combustible Gas Sensor.
NOTE
The high temperature characteristic has not been CSA verified above 75°C.
NOTE
Detector Electronics combustible gas detection K factors are not CSA verified.
NOTE
Metric straight thread types are for use in non-North American applications.
CALIBRATION
Calibration of the above listed sensors has been CSA verified using the Det-Tronics 225130-001 (50% LFL
methane) Calibration Kit.