Det-Tronics PIRECL - Other Approvals; SIL Approval; DNV Type Approval; DNV Application;Limitation

Det-Tronics PIRECL
69 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
C-2 95-8526
13.1
ATEX Special Conditions for Safe Use (‘X’):
• TheInfraredGasDetectormodelPIRECLshallbeinstalledinplaceswherethereisalowriskofmechanicaldamage.
• Theeldwiringterminalconnectionsarecertiedforasinglewireinsizefrom0.2to2.5mm
2
, (or two conductors
with same cross section 0.2 to 0.75 mm
2
).The screws must be tightened down with a torque 0.4 to 0.5 Nm.
• ThemetalhousingofthemodelPIRECLInfraredHydrocarbonGasDetectormustbeelectricallyconnectedtoearth
ground.
• TheintrinsicallysafeoutputontheHARTCommunicatorPortisinternallyconnectedtoearthground.
• TheInfraredGasDetectormodelPIRECLhasanambienttemperatureratingforperformanceof–55°Cto+75°C.
• Alarmoutputlatchingrequirement:Highalarmoutputsmustbeconguredaslatching,eitheraspartofthealarm
operation of the gas detector itself (in stand-alone applications), or as a function of the “high alarm” indication within
the controller that is directly connected to the gas detector (for remote applications).
Additional Safety Notes:
• Thefollowingwarningisontheproduct:Warning:Donotopenwhenanexplosivegasatmospheremaybepresent.
For ambient temperature above 60°C use field wiring suitable for maximum ambient temperature. For temperature
below –10°C use suitable field wiring for the lowest temperature.
• Theambienttemperaturerangeislimitedto–55°Cto+75°C(forExdversion)or–50°Cto+75°C(forExdeversion).
• Cable,bushingsandtheconduitentriesshallbeofatypealreadycertiedaccordingtorelevantATEXstandard,so
the protection principle employed will not be impaired.
• Unusedconduitentriesshallbeclosedusingstopplugscertiedfortheconditionsofuse(IP66/IP67minimum).The
stop plugs should be removable only with the aid of a tool.
• TheterminalcompartmentforEclipsewithoutrelaysisdesignedforeitheranincreasedsafety“e”terminationora
flameproof “d” termination of the supply cable. If a flameproof connection is chosen, then an ATEX certified cable
entry device certified to EN60079 must be used. The Eclipse with relays requires Ex d cable entry devices only.
• Shieldedcableisrequired.
EN Standards:
EN 50270: 2006
EN 50271: 2002
EN 60079-0: 2009
EN 60079-1: 2007
EN 60079-7: 2007
EN 60079-11: 2007
EN 60079-29-1: 2007
EN 60529: 1991+ A1 2000
EN 61000-6-4 (Emissions)
EN 61000-6-2 (Immunity)
CE: Conforms to:
Low Voltage Directive: 2006/95/EC,
EMC Directive: 2004/108/EC,
ATEX Directive: 94/9/EC.