Place the floor sensor in a conduit in an
appropriate place where it is not exposed
to sunlight or draft from door openings.
Equally distant and >2cm from two heat-
ing cables.
The conduit should be flush with the floor
surface - countersink the conduit if neces-
sary.
Route the conduit to the connection box.
The bending radius of the conduit must
be min 50mm.