AT 200 ENG
- 25 -
CURRENT OFFSET: Value offset
admitted of the current, expressed as
a percentage, compared to
calibration currents. If the values
measured exceed this threshold, the
FAULT relay will be triggered.
(Default = 10 %)
INITIAL DELAY: Time after the start
of the fans before analysing any
alarms. During this time the channels
will be displayed like this
and this .
(Default = 10 sec.)
ALARM DELAY: Error duration time
before activating an alarm.
(Default = 5 sec.)
CHANNEL 1: Channel 1
management:
0 = Disabled, 1 = Enabled.
(Default = 1)
N.B.: it isn’t possible to disable both
channels, in this case channel 1 will
be enabled.
CHANNEL 2: Channel 2
management:
0 = Disabled, 1 = Enabled.
(Default = 1)
N.B.: it isn’t possible to disable both
channels, in this case channel 1 will
be enabled.
At the end of the programming cycle, the control unit performs the calibration
and positions itself in the main menu.
For safety reasons, the time required for programming is in any case checked.
Over one minute from the start of the programming phase, the same is