31
5. Storage and Maintenance
• Operation
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at
25°C ambient temperature) has been exceeded, the batteries must be replaced. In this
case, please contact your dealer.
Be sure to deliver the spent battery to a recycling facility or sh
to your dealer in the replacement battery packing material
• Storage
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool,
dry location. During storage, recharge the battery in accordance with the following
table:
Storage Temperature Recharge Frequency Charging Duration
-25°C - 40°C Every 3 months 1-2 hours
40°C - 45°C Every 2 months 1-2 hours
6. Options
SNMP card: internal SNMP (options)
• Loosen the 2 torquescrews (on each side of the card).
• Carefully insert the SNMP card and lock the screws
The slot called SNMP supports the MEGAtec protocol. We advise that NetAgentII-3
port is also a tool to remotely monitor and manage any UPS system.
NetAgentII-3 Ports support the ModemDialin (PPP) function to enable the remote
control via the internet, when the network is unavailable.
In addition to the features of a standard NetAgentMini, NetAgentII has the option to
add NetFeelerLite to detect temperature, humidity, smoke and security sensors.
Thus, making NetAgentII a versatile management tool.NetAgentII also supports
multiple languages and is set up for web-based auto language detection.
Relaycard (options)
Mini dry contact card is used for providing the interface for UPS peripheral
monitoring. The contact signals can reflect UPS running status. The card is
connected to peripheral monitoring devices via terminal board to facilitate the