EasyManua.ls Logo

Dimplex SI 30TE - 12 Equipment Data; Performance Data

Dimplex SI 30TE
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
www.dimplex.de 452234.66.10 · FD 9407 EN-11
English
SI 30TE
12 Equipment Data
1 Type and order code
SI 30TE
2Design
2.1 Degree of protection according to EN 60 529 IP 21
2.2 Installation location Indoors
3 Performance data
3.1 Operating temperature limits:
Heating water flow °C up to 58 ± 2
Brine (heat source) °C -5 to +25
Antifreeze Monoethylene glycol
Minimum brine concentration (-13 °C freezing temperature) 25%
3.2 Temperature spread of heating water (flow/return flow) at B0 / W35
1
K
1. Operation with 2 compressors.
10.0 5.2
3.3 Heat output / COP at B-5 / W55
2
kW / ---
1
2. This data indicates the size and capacity of the system according to EN 255 or EN 14511. For an analysis of the economic and energy efficiency of the system, both the bivalence
point and the regulation should also be taken into consideration. The specified values, e.g. B10 / W55, have the following meaning: Heat source temperature 10 °C and heating
water flow temperature 55 °C.
24.7 / 2.4
kW / ---
3
3. Operation with 1 compressor.
9.0 / 1.7
at B0 / W45
2
kW / ---
1
28.7 / 3.3
kW / ---
3
12.0 / 2.7
at B0 / W50
2
kW / ---
1
28.1 / 2.9
kW / ---
3
11.3 / 2.4
at B0 / W35
2
kW / ---
1
31.2 / 4.6 30.3 / 4.4
kW / ---
3
14.4 / 4.2 14.1 / 4.1
3.4 Sound power level dB(A) 62
3.5 Sound pressure level at a distance of 1 m dB(A) 46
3.6 Heating water flow with an internal pressure differential of m³/h / Pa
2.6
4
/ 1100
4. Minimum heating water flow rate
5.0
5
/ 2500
5. Recommended heating water flow rate and brine throughput
3.7 Brine throughput with an internal pressure differential (heat source) of m³/h / Pa
7.0
5
/6000 7.0
5
/6000
3.8 Refrigerant / total filling weight type / kg R404A / 7.7
3.9 Lubricant / total filling weight type / litres Polyolester (POE) / 3.54
4 Dimensions, connections and weight
4.1 Device dimensions without connections
6
H x W x L mm
6. Note that additional space is required for pipe connections, operation and maintenance.
1660 x 1000 x 775
4.2 Device connections to heating system Inch G 1 1/2'' internal/external
4.3 Device connections to heat source Inch G 2'' internal/external
4.4 Weight of the transportable unit(s) incl. packing kg 365
5 Electrical connection
5.1 Nominal voltage; fuse protection V / A 400 / 20
5.2 Nominal power consumption
1
B0 W35 kW
6.78 6.91
5.3 Starting current with soft starter A 25
5.4 Nominal current B0 W35 / cos
2
A / ---
12.23 / 0.8 12.72 / 0.8
5.5 max. power consumption of compressor protection (per compressor) W 70
6 Complies with the European safety regulations
7
7. See CE declaration of conformity
7 Additional model features
7.1 Water in device protected against freezing
8
8. The heat circulating pump and the heat pump manager must always be ready for operation.
Yes
7.2 Performance levels 2
7.3 Controller internal/external Internal

Table of Contents