EN-8
8.1
English
 
 
Sets the temperature value by which the heating characteristic
curve of heating circuit 1 is to be raised when the temperature is
raised.
0K
...
19K
 
  
For each day of the week, it is possible to select whether Time1,
Time2, no time or both times are to be active when the
temperature is raised. Operations to raise the temperature that
exceed a weekday are activated or deactivated at the end of each
day accordingly.
N
T1
T2
Y
 
  
Sets the desired return flow set temperature when dynamic cooling
is selected.
10°C
... 15°C ...
30°C
 
   
Sets the room set temperature for silent cooling.
The actual value is measured by room climate control station 1.
15.0°C
... 20.0°C ...
30.0°C
  
Settings for heating circuit 2/3.
  

Settings to lower the heating characteristic curve of heating circuit
2/3.
  


Sets the time during which the temperature in heating circuit 2/3 is
to be lowered.
00:00
...
23:59
  
 
Sets the temperature value by which the heating characteristic
curve of heating circuit 2/3 is to be lowered when the temperature
is lowered.
0K
...
19K
  
  
For each day of the week, it is possible to select whether Time1,
Time2, no time or both times are to be active when the
temperature is lowered. Operations to lower the temperature that
exceed a weekday are activated or deactivated at the end of each
day accordingly.
N
T1
T2
Y
  

Settings to raise the heating characteristic curve of heating circuit
2/3.
 


Sets the time during which the temperature in heating circuit 2/3 is
to be raised.
00:00
...
23:59
 
 
Sets the temperature value by which the heating characteristic
curve of heating circuit 2/3 is to be raised when the temperature is
raised.
0K
...
19K
 
  
For each day of the week, it is possible to select whether Time1,
Time2, no time or both times are to be active when the
temperature is raised. Operations to raise the temperature that
exceed a weekday are activated or deactivated at the end of each
day accordingly.
N
T1
T2
Y
   
   
Sets the room set temperature for silent cooling.
The actual value is measured by room climate control station 1/2.
15.0°C
... 20.0°C ...
30.0°C

Settings for cooling operation.
 

Sets the time programs for dynamic cooling.
  


Sets the times during which dynamic cooling is blocked. 00:00
...
23:59
  
  
For each day of the week, it is possible to select whether Time1,
Time2, no time or both times are to be active for a block. Blocks
that exceed a weekday are activated or deactivated at the end of
each day accordingly.
N
T1
T2
Y
 System-specific parameters Setting range

Other manuals for Dimplex WPM 2006 R

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dimplex WPM 2006 R and is the answer not in the manual?

Dimplex WPM 2006 R Specifications

General IconGeneral
BrandDimplex
ModelWPM 2006 R
CategoryNetwork Router
LanguageEnglish

Related product manuals