EN-9
Menu Structure 8.1
English
Setting for DHW preparation
Sets the desired hot water temperature 30°C
... 60°C ...
85°C
Sets the time programs for hot water blocks
Sets the times in which DHW preparation is blocked 00:00
...
23:59
For each day of the week, it is possible to select whether Time1,
Time2, no time or both times are to be active when the
temperature is lowered. Operations to lower the temperature that
exceed a weekday are activated or deactivated at the end of each
day accordingly.
N
T1
T2
Y
To carry out a thermal disinfection, the DHW is heated up once to
the desired temperature. The heating period is terminated
automatically when the set temperature is reached, at 12:00 p.m.
or after 4 hours at the latest.
Sets the start time for the thermal disinfection 00:00
...
23:59
Sets the desired hot water temperature which is to be reached
during thermal disinfection
60°C
... 65°C ...
85°C
For each day of the week, it is possible to select whether thermal
disinfection is desired at the set start time.
N
Y
The circulation pump is controlled by a timer function
Sets the times at which the circulation pump is to be activated 00:00
23:59
For each day of the week, it is possible to select whether the
circulation pump is activated at the set start time.
No
Yes
Sets the preparation of swimming pool water
Sets the desired swimming pool temperature 5°C
... 25°C ...
60°C
Sets the desired swimming pool temperature with parallel cooling
operation
Sets whether the waste heat recovery during cooling is dependent
on the switching status of the thermostat or in continuous
operation
5°C
... 25°C ...
60°C
Sets the time programs for swimming pool blocks 1K
...
20K
Sets the times in which swimming pool water preparation is
blocked
00:00
...
23:59
For each day of the week, it is possible to select whether Time1,
Time2, no time or both times are to be active when the
temperature is lowered. Operations to lower the temperature that
exceed a weekday are activated or deactivated at the end of each
day accordingly.
N
T1
T2
Y
System-specific parameters Setting range