24
Channel
Channel selection
Default value = 10
Range is: 10 to 26
Conditional parameter to Wireless models
This parameter will only appear when a wireless network
adapter is present. If the thermostat is installed with a
BACnet or LonWorks adapter, this parameter will not be
used or displayed
This parameter (Channel) is used to link specific
thermostats to specific wireless gateway(s) ( EC-BOS )
For every thermostat reporting to a gateway ( maximum
of 30 thermostats per gateway ), be sure you set the
SAME channel value both at the gateway and the
thermostat(s).
Distech Controls recommends using only the 2 last
channels ( 25-@ 2575MHz and 26-@ 2580MHz )
The default value of 10 is NOT a valid channel. The valid
range of available channel is from 11 to 26
DI 1
Digital input no.1 configuration
Open contact input = function not
energized
Closed contact input = function energized
Default value = None
None, No function will be associated with the input
Rem NSB, remote NSB timer clock input. Will disable
the internal scheduling of the thermostat. The scheduling
will now be set as per the digital input. The time is still
displayed as information, but the menu part related to
scheduling is disabled and no longer accessible.
Open contact = occupied setpoints
Closed contacts = unoccupied setpoints
RemOVR Temporary override remote contact. Disables
all override menu function of the thermostat. The
override function is now controlled by a manual remote
momentarily closed contact. When configured in this
mode, the input operates in a toggle mode. With this
function enabled it is now possible to toggle between
unoccupied & occupied setpoints for the amount of time
set by parameter (TOccTime) temporary occupancy
time. When Override is enabled, an Override status
message will be displayed
Filter, a back-lit flashing Filter alarm will be displayed on
the thermostat LCD screen when the input is energized
Service, a back-lit flashing Service alarm will be
displayed on the thermostat LCD screen when the input
is energized
Fan lock, a back-lit flashing Fan lock alarm will be
displayed on the thermostat LCD screen when the input
is not energized. Used in conjunction with a local airflow
sensor connected to the input. Locks out the thermostat
heating and cooling action if no airflow is detected 10
seconds after the fan ( G terminal ) is energized.
Open contact = no airflow
Closed contacts = airflow present
DI 2
Digital input no. 2 configuration
Default value = None
Same as above. It is possible to configure both inputs to
have the same function.
MenuScro
Menu scroll
Default value = On = Scroll active
Removes the scrolling display and only present the room
temperature/humidity to the user. With this option
enabled, no status is given of mode, schedule and
outdoor temperature.
On = Scroll active
Off = Scroll not active
lockout
Keypad lockout levels
0 = No lock
1 = Low level